Development of a new pole–slip protection function for synchronous machines
dc.contributor.author | Lamont, Lafras | |
dc.date.accessioned | 2013-12-05T07:05:36Z | |
dc.date.available | 2013-12-05T07:05:36Z | |
dc.date.issued | 2011 | |
dc.description | PhD (Electrical Engineering), North-West University, Potchefstroom Campus, 2011 | |
dc.description.abstract | The rotor shaft of a synchronous machine can experience severe mechanical stress due to torque pulsations during a pole-slip condition. All pole-slip protection relays currently on the market use the impedance pole-slip protection method to detect a pole-slip. No commercial relay currently available can predict accurately when a generator is about to experience a damaging pole-slip. All the relays will only trip a generator after it has pole-slipped one or more times. Severe mechanical damage could be caused to a machine after only one pole-slip. It is therefore essential to enhance pole-slip protection relays to such an extent that it can trip a generator before it pole slips. The proposed pole-slip protection function must predict when a generator will become unstable during a network fault. As soon as instability is predicted, the generator must be tripped before the fault is cleared to avoid damaging post-fault torque effects. Conventional impedance pole-slip protection methods are are also discussed and the shortcomings of impedance pole-slip protection are investigated. The new pole-slip protection function was designed by using PSCAD. Detailed PSCAD simulations on different network configurations proved that the new pole-slip protection function will trip a generator before a damaging pole-slip occurs. The new pole-slip protection function was also implemented on an ABB REM543 multifunctional protection relay and tested on a RTDS. The concept of the new pole-slip function was successfully demonstrated on the protection relay. The operation of conventional impedance scheme relays was compared with the proposed pole-slip function for different fault conditions. Although the new pole-slip protection function is more complex than the existing impedance functions, it was concluded that similar skills are required to test and commission the new protection function. The new pole-slip function outperforms the impedance protection methods, since the new protection function can trip the generator before it pole-slips. | en_US |
dc.description.thesistype | Doctoral | en_US |
dc.identifier.uri | http://hdl.handle.net/10394/9730 | |
dc.language.iso | en | en_US |
dc.publisher | North-West University | |
dc.subject | Synchronous generators | en_US |
dc.subject | Pole-slip protection | en_US |
dc.subject | Out-of-step | en_US |
dc.subject | Power system stability | en_US |
dc.subject | Powerswing | en_US |
dc.subject | Equal area criteria | en_US |
dc.subject | Impedance protection | en_US |
dc.title | Development of a new pole–slip protection function for synchronous machines | en |
dc.type | Thesis | en_US |
Files
Original bundle
1 - 5 of 9
Loading...
- Name:
- Lamont_L_TOC.pdf
- Size:
- 171.83 KB
- Format:
- Adobe Portable Document Format
- Description:
- Table of contents
Loading...
- Name:
- Lamont_L_Chapter_1.pdf
- Size:
- 238.66 KB
- Format:
- Adobe Portable Document Format
- Description:
- Chapter 1
Loading...
- Name:
- Lamont_L_Chapter_2.pdf
- Size:
- 1.36 MB
- Format:
- Adobe Portable Document Format
- Description:
- Chapter 2
Loading...
- Name:
- Lamont_L_Chapter_3.pdf
- Size:
- 824.33 KB
- Format:
- Adobe Portable Document Format
- Description:
- Chapter 3
Loading...
- Name:
- Lamont_L_Chapter_4.pdf
- Size:
- 810.34 KB
- Format:
- Adobe Portable Document Format
- Description:
- Chapter 4
License bundle
1 - 1 of 1
Loading...
- Name:
- license.txt
- Size:
- 1.61 KB
- Format:
- Item-specific license agreed upon to submission
- Description: