Show simple item record

dc.contributor.authorBissett, J.V.
dc.contributor.authorVan Vuuren, P.A.
dc.date.accessioned2018-07-20T07:33:38Z
dc.date.available2018-07-20T07:33:38Z
dc.date.issued2018
dc.identifier.citationBissett, J.V. & Van Vuuren, P.A. 2018. Off Line Partial Discharge as an essential Condition Based Monitoring (CBM) Tool for busbar insulation monitoring on Air Insulated Switchgear (AIS). (In Heyns, P.S., Van Vuuren, P.A., Van Schoor, G. & Rao, R.B.K.N., eds. Proceedings of the 31st International Congress and Exhibition on Condition Monitoring and Diagnostic Engineering Management (COMADEM), 2-5 July 2018, Sun City, Rustenburg, South Africa. p.95-106). [http://www.comadem2018.com/]en_US
dc.identifier.issn978-1-86822-691-7
dc.identifier.urihttp://hdl.handle.net/10394/28609
dc.identifier.urihttp://www.comadem2018.com/
dc.description.abstractThis paper investigates the effectiveness of current test methods and procedures associated with insulation testing on the busbar of Air Insulated Switchgear (AIS) during scheduled planned maintenance. An improved test method proposes combining traditional AC voltage withstand test with Partial Discharge (PD) measurement. Three PD sensors were considered, namely Airborne Acoustic (AA), Transient Earth Voltage (TEV) and High Frequency Current Transformer (HFCT). The results confirm that HFCT is most sensitive and revealed significant difference at higher voltages between the six AIS samples. The TEV results produced consistent readings with smaller differences at higher voltages. The Ultra-sound instrument was found to be extremely sensitive but lack the capability to produce reliable measurement readings. Peak TEV measurements indicate a noticeable difference between older and newer samplesen_US
dc.language.isoenen_US
dc.publisherNWUen_US
dc.subjectAir Insulated Switchgear (AIS)en_US
dc.subjectRemaining Useful Life (RUL)en_US
dc.subjectCondition Based Monitoring (CBM)en_US
dc.subjectPartial Discharge (PD)en_US
dc.subjectOn Line Partial Discharge (OLPD)en_US
dc.titleOff Line Partial Discharge as an essential Condition Based Monitoring (CBM) Tool for busbar insulation monitoring on Air Insulated Switchgear (AIS)en_US
dc.typePresentationen_US
dc.contributor.researchID10732926 - Van Vuuren, Pieter Andries