Testing of a predictive pole-slip protection algorithm on a real time digital simulator
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE
Abstract
Predictive pole-slip protection is not implemented in commercially available protection relays. All pole-slip protection relays on the market will only trip a generator after it has pole-slipped one or more times. A predictive pole-slip protection algorithm was developed that can trip a generator before a pole-slip occurs. The Predictive Pole-Slip algorithm was tested on a Real Time Digital Simulator. This paper explains the testing setup as well as the scenarios tested. The feasibility of predictive pole-slip protection algorithm in a practical application is also discussed
Description
Citation
Lamont, L. et al. 2016. Testing of a predictive pole-slip protection algorithm on a real time digital simulator. IEEE International Workshop on Applied Measurements for Power Systems (AMPS), 28-30 Sept: # 7602875. [https://doi.org/10.1109/AMPS.2016.7602875]