Rens, SanéRens, JohanHolm, JohannBotha, GerhardDesmet, Jan2019-01-302019-01-302018Rens, S. et al. 2018. On the remote calibration of voltage transformers: validation of opportunity. Proceedings of the IEEE 9th International Workshop on Applied Measurements for Power Systems (AMPS), 26-28 Sep, Bologna, Italy: Article no 8494862. [https://doi.org/ 10.1109/AMPS.2018.8494862]978-1-5386-5375-3 (Online)2475-2304 (Online)http://hdl.handle.net/10394/31770https://ieeexplore.ieee.org/document/8494862https://doi.org/ 10.1109/AMPS.2018.8494862Remote calibration of instrument transformers seems possible if sufficient certainty in field measurements can be achieved. This opportunity, until now, was only investigated from a theoretical point of view and in this paper, is now further investigated by using real-life synchrophasors. A transmission line is emulated, and voltage and current synchrophasors collected across the transmission line by two different synchrophasor recorders to derive a ratio correction factor for the remote instrument transformersenInstrument transformersRatio correction factorLeast squares estimateMeasurement uncertaintyPhasor measurement unitsTransmission line parametersGPS timestampingOn the remote calibration of voltage transformers: validation of opportunityPresentation